AILV-watermarked cover of document GBTG100571122

Fire resistance

100 mm Single MgO-Lined Rock Wool Panel

180 min under the reported test conditions

GBTG100571122

Read Results & Test Conditions

A commissioned test report covering a 100 mm single glass-magnesium (MgO) and rock wool panel, including listed material properties and fire-resistance results.

Document number
GBTG100571122
Thickness
100 mm
Standards
GB/T 25975-2018; GB/T 9978.1-2008
Issue date
2025-09-05
Applicant / holder
浙江艾绿净化科技有限公司
Issuing organization
广东省宝通质量检测有限公司

Recorded Results

Appearance Pass
Panel thickness 100 mm
Prepainted steel facing thickness 0.5 mm
MgO board layer thickness 5 mm
Density (as labelled in report) 120 kg/m³
Thermal conductivity 0.038 W/(m·K)
Tensile strength 65 kPa
Moisture absorption by mass 2.1 %
Water repellency 99.5 %
Acidity coefficient 1.8
Fire resistance under reported test conditions 180 min

Sample and Test Conditions

  • Three client-submitted specimens. The reported layers include 0.5 mm prepainted steel facing and a 5 mm MgO board layer.
  • At 180 min, mean unexposed-face temperature rise was 89 °C and maximum rise was 97 °C.
  • Density and thermal-conductivity values are transcribed using the original table labels; the table does not separately identify them as core-only or whole-panel values.

Results describe the submitted 100 mm construction. They do not establish the performance of a 50 mm panel or another build-up.

Related: Cleanroom Panels

AILV-watermarked cover of document 2024200016

Fire resistance

100 mm Double MgO-Lined Rock Wool Panel

240 min under the reported test conditions

2024200016

Read Results & Test Conditions

A fire-resistance report for a 100 mm metal-faced rock wool wall assembly with MgO board linings on both sides.

Document number
2024200016
Thickness
100 mm
Standards
GB/T 9978.1-2008; GB/T 9978.8-2008
Issue date
2024-01-23
Applicant / holder
浙江艾绿净化科技有限公司
Issuing organization
应急管理部四川消防研究所(SCFRI)/国家防火建筑材料质量检验检测中心(NFTC)

Recorded Results

Fire resistance under reported test conditions 240 min
Integrity 240 min: no flame on unexposed face; cotton pad did not ignite; gap-gauge test not performed.
Insulation At 240 min, mean unexposed-face temperature rise 61 °C; maximum rise 76 °C.
Deflection at geometric centre +33 mm at 240 min (positive towards fire-exposed face)

Sample and Test Conditions

  • Four specimens, each 3000 x 1000 x 100 mm; vertical, non-loadbearing assembly with a 3000 x 3000 mm exposed area and restrained perimeter.
  • Build-up shown: 0.5 mm steel / 5 mm MgO / 89 mm rock wool (100 kg/m³) / 5 mm MgO / 0.5 mm steel. Joints, fixing and edge restraint follow the report drawing.

Assembly-specific fire result under the listed GB/T methods and reported installation conditions. The result is not relabelled as an EN EI classification.

Related: Cleanroom Panels

AILV-watermarked cover of document GBT312748721

Fire resistance

100 mm Double Gypsum-Lined Rock Wool Panel

240 min under the reported test conditions

GBT312748721

Read Results & Test Conditions

A commissioned test report covering a 100 mm handmade rock wool panel with gypsum board layers on both sides, including listed material properties and fire resistance.

Document number
GBT312748721
Thickness
100 mm
Standards
GB/T 25975-2018; GB/T 9978.1-2008
Issue date
2025-11-18
Applicant / holder
浙江艾绿净化科技有限公司
Issuing organization
广东省宝通质量检测有限公司

Recorded Results

Appearance Pass
Panel thickness 100 mm
Prepainted steel facing thickness 0.5 mm
Gypsum board layer thickness 9.5 mm upper layer; 9.5 mm lower layer
Density (as labelled in report) 120 kg/m³
Thermal conductivity 0.029 W/(m·K)
Tensile strength 69 kPa
Moisture absorption by mass 0.9 %
Water repellency 99.7 %
Acidity coefficient 2.1
Fire resistance under reported test conditions 240 min

Sample and Test Conditions

  • Three client-submitted specimens. Each steel facing is 0.5 mm; the upper and lower gypsum-board layers are each 9.5 mm.
  • At 240 min, mean unexposed-face temperature rise was 96 °C and maximum rise was 104 °C.
  • Density and thermal-conductivity values retain the source table labels; no unsupported whole-panel or core-only interpretation is added.

Results describe the submitted 100 mm double-gypsum construction. They do not establish the performance of a 50 mm panel or an MgO-lined construction.

Related: Cleanroom Panels

AILV-watermarked cover of document 2025210281

Fire resistance

100 mm Rock Wool Sandwich Panel

180 min under the reported test conditions

2025210281

Read Results & Test Conditions

A fire-resistance report for a 100 mm metal-faced rock wool wall assembly without an MgO or gypsum board lining in the reported drawing.

Document number
2025210281
Thickness
100 mm
Standards
GB/T 9978.1-2008; GB/T 9978.8-2008
Issue date
2025-06-10
Applicant / holder
浙江艾绿净化科技有限公司
Issuing organization
应急管理部四川消防研究所(SCFRI)/国家防火建筑材料质量检验检测中心(NFTC)

Recorded Results

Fire resistance under reported test conditions 180 min
Integrity 180 min: no flame on unexposed face; cotton pad did not ignite; gap-gauge test not performed.
Insulation At 180 min, mean unexposed-face temperature rise 37 °C; maximum rise 89 °C.
Deflection at geometric centre +16 mm at 180 min (positive towards fire-exposed face)

Sample and Test Conditions

  • Four specimens, each 3000 x 1000 x 100 mm; vertical, non-loadbearing assembly with a 3000 x 3000 mm exposed area and restrained perimeter.
  • Drawing: 0.5 mm prepainted steel facings and 100 kg/m³ rock wool; no MgO board layer is shown. Joints, seam covers and fixing follow the report.

The 180-minute result applies to the reported 100 mm vertical assembly, including its joints, fixings and edge restraint.

Related: Cleanroom Panels

AILV-watermarked cover of document CTTC202507220001

Reaction to fire

13 mm Steel-Faced Aluminium Honeycomb Infill Panel

GB 8624-2012: A(A2)

CTTC202507220001

Read Results & Test Conditions

A reaction-to-fire test report for a 13 mm prepainted steel-faced aluminium honeycomb infill panel. The report states A(A2) under GB 8624-2012.

Document number
CTTC202507220001
Thickness
13 mm
Standards
GB 8624-2012; GB/T 5464-2010; GB/T 20284-2006
Issue date
2025-08-04
Applicant / holder
浙江艾绿净化科技有限公司
Issuing organization
浙江科泰检测认证有限公司

Recorded Results

Reaction-to-fire classification A(A2) under GB 8624-2012 for flat building materials and products, as stated in report
Fire growth rate index 4.6 W/s
Lateral flame spread Did not reach the long edge of the specimen
Total heat release over 600 s 0.5 MJ
Furnace temperature rise 0.3 C
Mass loss 0.1 %
Sustained flaming time 0 s
Specimen density 655.0 kg/m³

Sample and Test Conditions

  • Commissioned test on specimens supplied by the client; production date 20 July 2025.
  • The SBI installation note states no fixed substrate panel; the specimen backboard was 12 mm calcium-silicate board, with the decorative face exposed to fire.

A(A2) is the GB 8624-2012 reaction-to-fire designation stated in this report; it is distinct from fire-resistance duration and is not presented as an EN classification.

Related: Cleanroom Ceiling Panels

AILV-watermarked cover of document WPGY241757

Commissioned load test

13 mm Steel-Faced Aluminium Honeycomb Infill Panel

150 kg total test load in the specified support frame

WPGY241757

Read Results & Test Conditions

A commissioned load test of one 13 mm prepainted steel-faced aluminium honeycomb infill panel in a defined four-point support frame.

Document number
WPGY241757
Thickness
13 mm
Standards
Enterprise technical conditions (no numbered standard stated)
Issue date
2024-05-10
Applicant / holder
浙江艾绿净化科技有限公司
Issuing organization
苏州市产品质量监督检验院

Recorded Results

Applied uniformly distributed load 150 kg total
Reported result Pass: no fracture under the stated arrangement
Specimen size 1170 x 1170 mm
Support arrangement Four points; 900 mm spacing in the same direction

Sample and Test Conditions

  • One specimen, 1170 x 1170 mm, in a 1200 x 1200 mm support frame with four support points. Support spacing in the same direction: 900 mm.
  • Applied load: 150 kg, uniformly distributed. Stated requirement: no fracture. The report records a pass.

The source notice limits reports without CMA/CNAS recognition marks to research, teaching or internal quality control. This sample result is not presented as accredited certification, a kg/m² rating or permission for people to walk on a ceiling.

Related: Cleanroom Ceiling Panels

AILV-watermarked cover of document HJC7802507QMS142R0S

ISO 9001 / QMS

Quality Management System Certificate

Printed scope: sales of metal sandwich panels.

HJC7802507QMS142R0S

Read Results & Test Conditions

An ISO 9001 quality management system certificate naming Zhejiang Ailv Purification Technology Co., Ltd. Its printed scope is sales of metal sandwich panels.

Document number
HJC7802507QMS142R0S
Standards
GB/T 19001-2016 / ISO 9001:2015
Issue date
2025-07-31
Applicant / holder
浙江艾绿净化科技有限公司
Issuing organization
北京华夏钜星质量认证有限公司

Certificate Information

Printed certified scope Sales of metal sandwich panels
Initial certification 31 July 2025
Current certificate date 31 July 2025
Printed expiry date 30 July 2028
IAF sector code 29

Scope and Certificate Conditions

  • Registered address: No. 186 Ganghang Avenue, Meixi Industrial Park, Anji County, Huzhou, Zhejiang, China.
  • The certificate states that at least one surveillance audit is required each year and that the certificate is used with the surveillance notice.

The printed scope is sales, not a stated manufacturing scope or product-performance certification. The downloadable document is an AILV-watermarked viewing copy; the untouched source certificate is retained separately.

Related: About AILV

AILV-watermarked cover of document 2023200611

Fire resistance

50 mm Composite-Core Fire-Resistant Sandwich Panel

60 min integrity and insulation; reported 50 mm wall assembly.

2023200611

Read Results & Test Conditions

A fire-resistance report for the stated 50 mm metal-faced sandwich wall construction. The tested vertical assembly maintained fire integrity and insulation for 60 minutes.

Document number
2023200611
Thickness
50 mm
Standards
GB/T 9978.1-2008; GB/T 9978.8-2008
Issue date
2023-08-28
Applicant / holder
浙江艾绿净化科技有限公司
Issuing organization
应急管理部四川消防研究所(SCFRI)/国家防火建筑材料质量检验检测中心(NFTC)

Recorded Results

Fire integrity 60 min
Fire insulation 60 min
Mean unexposed-face temperature rise 64 °C at 60 min
Maximum unexposed-face temperature rise 92 °C at 60 min

Sample and Test Conditions

  • Drawing: 0.5 mm color-coated steel facings and a composite fire-resistant board core with reported density 220 kg/m³. The drawing lists glass-magnesium, magnesium oxide, magnesium oxysulfate, perlite, EPS particles and glass-fibre mesh among its ingredients.
  • Four client-supplied specimens, each 3000 x 1000 x 50 mm; vertical assembly with a 3000 x 3000 mm exposed area, perimeter restraint and joints fixed as shown in the report.

The results apply to the tested construction, joints and fixing arrangement under the stated GB/T methods. Fire-resistance duration is distinct from reaction-to-fire classification.

AILV-watermarked cover of document 2023200610

Fire resistance

50 mm Single MgO-Lined Rock Wool Panel

90 min integrity and insulation; reported 50 mm wall assembly.

2023200610

Read Results & Test Conditions

A fire-resistance report for the stated 50 mm metal-faced sandwich wall construction. The tested vertical assembly maintained fire integrity and insulation for 90 minutes.

Document number
2023200610
Thickness
50 mm
Standards
GB/T 9978.1-2008; GB/T 9978.8-2008
Issue date
2023-08-28
Applicant / holder
浙江艾绿净化科技有限公司
Issuing organization
应急管理部四川消防研究所(SCFRI)/国家防火建筑材料质量检验检测中心(NFTC)

Recorded Results

Fire integrity 90 min
Fire insulation 90 min
Mean unexposed-face temperature rise 55 °C at 90 min
Maximum unexposed-face temperature rise 60 °C at 90 min

Sample and Test Conditions

  • Drawing: 0.5 mm color-coated steel facings, rock wool core (100 kg/m³) and a single 5 mm glass-magnesium (MgO) board lining.
  • Four client-supplied specimens, each 3000 x 1000 x 50 mm; vertical assembly with a 3000 x 3000 mm exposed area, perimeter restraint and joints fixed as shown in the report.

The results apply to the tested construction, joints and fixing arrangement under the stated GB/T methods. Fire-resistance duration is distinct from reaction-to-fire classification.

Related: 50 mm Single Magnesium & Rockwool Panel

AILV-watermarked cover of document GBT312748723

Fire resistance & material properties

50 mm Single Gypsum-Lined Rock Wool Panel

90 min fire result, plus listed material properties.

GBT312748723

Read Results & Test Conditions

A commissioned report covering a 50 mm handmade rock wool panel with a single 12 mm gypsum board lining and 0.5 mm color-coated steel facings.

Document number
GBT312748723
Thickness
50 mm
Standards
GB/T 25975-2018; GB/T 9978.1-2008
Issue date
2025-10-21
Applicant / holder
浙江艾绿净化科技有限公司
Issuing organization
广东省宝通质量检测有限公司

Recorded Results

Appearance Pass
Panel thickness 50 mm
Steel facing thickness 0.5 mm
Gypsum lining thickness 12 mm
Reported density 120 kg/m³
Thermal conductivity 0.036 W/(m·K)
Tensile strength 67 kPa
Moisture absorption by mass 0.8%
Water repellency 99.3%
Acidity coefficient 1.9
Fire integrity and insulation 90 min

Sample and Test Conditions

  • Three client-submitted specimens. Testing: 9-21 October 2025.
  • At 90 min, mean unexposed-face temperature rise was 86 °C and maximum rise was 90 °C.
  • The report does not include a complete assembly drawing. The density field is retained as reported, without adding a core-only or whole-panel interpretation.

This report covers a single gypsum lining with rock wool. It is distinct from a double-gypsum, MgO-lined or paper-honeycomb construction.

AILV-watermarked cover of document 2024200308

Fire resistance

50 mm Double MgO-Lined Rock Wool Panel

120 min integrity and insulation; reported 50 mm wall assembly.

2024200308

Read Results & Test Conditions

A fire-resistance report for the stated 50 mm metal-faced sandwich wall construction. The tested vertical assembly maintained fire integrity and insulation for 120 minutes.

Document number
2024200308
Thickness
50 mm
Standards
GB/T 9978.1-2008; GB/T 9978.8-2008
Issue date
2024-05-23
Applicant / holder
浙江艾绿净化科技有限公司
Issuing organization
应急管理部四川消防研究所(SCFRI)/国家防火建筑材料质量检验检测中心(NFTC)

Recorded Results

Fire integrity 120 min
Fire insulation 120 min
Mean unexposed-face temperature rise 55 °C at 120 min
Maximum unexposed-face temperature rise 64 °C at 120 min

Sample and Test Conditions

  • Drawing: 0.5 mm steel / 5 mm MgO board / rock wool (100 kg/m³) / 5 mm MgO board / 0.5 mm steel.
  • Four client-supplied specimens, each 3000 x 1000 x 50 mm; vertical assembly with a 3000 x 3000 mm exposed area, perimeter restraint and joints fixed as shown in the report.

The results apply to the tested construction, joints and fixing arrangement under the stated GB/T methods. Fire-resistance duration is distinct from reaction-to-fire classification.

Related: 50 mm Double Magnesium & Rockwool Panel

AILV-watermarked cover of document 2024200015

Fire resistance

50 mm Double Gypsum-Lined Paper Honeycomb Panel

60 min integrity and insulation; reported 50 mm wall assembly.

2024200015

Read Results & Test Conditions

A fire-resistance report for the stated 50 mm metal-faced sandwich wall construction. The tested vertical assembly maintained fire integrity and insulation for 60 minutes.

Document number
2024200015
Thickness
50 mm
Standards
GB/T 9978.1-2008; GB/T 9978.8-2008
Issue date
2024-01-23
Applicant / holder
浙江艾绿净化科技有限公司
Issuing organization
应急管理部四川消防研究所(SCFRI)/国家防火建筑材料质量检验检测中心(NFTC)

Recorded Results

Fire integrity 60 min
Fire insulation 60 min
Mean unexposed-face temperature rise 36 °C at 60 min
Maximum unexposed-face temperature rise 66 °C at 60 min

Sample and Test Conditions

  • Drawing: 0.5 mm steel / 9.5 mm gypsum / 30 mm paper honeycomb / 9.5 mm gypsum / 0.5 mm steel.
  • Four client-supplied specimens, each 3000 x 1000 x 50 mm; vertical assembly with a 3000 x 3000 mm exposed area, perimeter restraint and joints fixed as shown in the report.

The results apply to the tested construction, joints and fixing arrangement under the stated GB/T methods. Fire-resistance duration is distinct from reaction-to-fire classification.

AILV-watermarked cover of document 2024200307

Fire resistance

50 mm Rock Wool Sandwich Panel

60 min integrity and insulation; reported 50 mm wall assembly.

2024200307

Read Results & Test Conditions

A fire-resistance report for the stated 50 mm metal-faced sandwich wall construction. The tested vertical assembly maintained fire integrity and insulation for 60 minutes.

Document number
2024200307
Thickness
50 mm
Standards
GB/T 9978.1-2008; GB/T 9978.8-2008
Issue date
2024-05-23
Applicant / holder
浙江艾绿净化科技有限公司
Issuing organization
应急管理部四川消防研究所(SCFRI)/国家防火建筑材料质量检验检测中心(NFTC)

Recorded Results

Fire integrity 60 min
Fire insulation 60 min
Mean unexposed-face temperature rise 59 °C at 60 min
Maximum unexposed-face temperature rise 66 °C at 60 min

Sample and Test Conditions

  • Drawing: 0.5 mm color-coated steel facings and a 100 kg/m³ rock wool core. No MgO or gypsum board lining is shown.
  • Four client-supplied specimens, each 3000 x 1000 x 50 mm; vertical assembly with a 3000 x 3000 mm exposed area, perimeter restraint and joints fixed as shown in the report.

The results apply to the tested construction, joints and fixing arrangement under the stated GB/T methods. Fire-resistance duration is distinct from reaction-to-fire classification.

Related: 50 mm Rockwool Panel

AILV-watermarked cover of document CBT10502181959

Air permeability & construction

Steel Cleanroom Door

Tested door: 900 x 2100 mm; construction and air-leakage results.

CBT10502181959

Read Results & Test Conditions

A commissioned report covering construction, assembly and air-permeability tests on a 900 x 2100 mm steel cleanroom door.

Document number
CBT10502181959
Standards
GB/T 7106-2019; GB/T 8478-2020. Assessment: enterprise technical requirements.
Issue date
2025-10-22
Applicant / holder
浙江艾绿净化科技有限公司
Issuing organization
广东省宝通质量检测有限公司

Recorded Results

Tested specimen 900 x 2100 mm; one door set
Frame / leaf assembly clearance 0.2 mm
Air leakage per unit opening-joint length, q1 2.4 m³/(m·h); both reported entries
Air leakage per unit area, q2 6.9 m³/(m²·h); both reported entries
Appearance, assembly and construction Pass
Overall conclusion Tested items met the stated requirements; pass

Sample and Test Conditions

  • Client-submitted specimen received 7 October 2025. Testing took place 10-22 October 2025.
  • The dimensional ranges listed as additional models in the source are not represented as separately tested specimens.

Air-permeability values are retained with their reported units. No unstated pressure condition, air-leakage class or fire-resistance rating is added.

Related: Cleanroom Doors & Windows

AILV-watermarked cover of document CBT10502181960

Safety & durability

High-Speed Roll-Up Door

Tested door: 2000 x 3000 mm; safety and 10,000-cycle results.

CBT10502181960

Read Results & Test Conditions

A commissioned report covering dimensions, operation, anti-entrapment safety, electrical safety and durability of a high-speed roll-up door.

Document number
CBT10502181960
Standards
JG/T 302-2022. Assessment: enterprise technical requirements.
Issue date
2025-10-22
Applicant / holder
浙江艾绿净化科技有限公司
Issuing organization
广东省宝通质量检测有限公司

Recorded Results

Tested specimen 2000 x 3000 mm; one door set
Curtain thickness 1.1 mm
End-stop repeatability 7 mm
Non-contact sensor response 0.6 s, reverse operation; failure rate 0 in 100 tests
Contact safety-edge trigger force / response 136 N / 0.3 s
Power-off falling distance 0 mm; fall-arrest lock immediately engaged
Manual release force 85 N
Protective earth resistance 0.012 ohm
Electric strength 1000 V for 1 min: no breakdown or flashover
Leakage current 0.028 mA
Continuous operation 10,000 cycles: no tearing; speed deviation no more than 5%; anti-entrapment response 0.7 s
After 30-day stationary test Smooth operation; reported leakage rate 0.32 m³/(m·h)
Overall conclusion Tested items met the stated requirements; pass

Sample and Test Conditions

  • Client-submitted specimen received 7 October 2025. Testing took place 10-22 October 2025.
  • Durability and response values are reported test observations for the submitted specimen. Additional result tables and qualifiers remain in the complete source report.

The English summary does not add a door opening speed, because none is stated in the reviewed results. Additional dimensional models listed in the source are not represented as separately tested specimens.

Related: Cleanroom Doors & Windows

AILV-watermarked cover of document CBT10502181961

Glazing & watertightness

Double-Glazed Cleanroom Vision Window

400 Pa for 15 min: no leakage in the reported watertightness test.

CBT10502181961

Read Results & Test Conditions

A commissioned report covering construction, fragmentation and watertightness of a double-glazed vision window.

Document number
CBT10502181961
Standards
GB 15763.2-2005; GB/T 7106-2019; GB/T 8478-2020. Assessment: enterprise technical requirements.
Issue date
2025-10-22
Applicant / holder
浙江艾绿净化科技有限公司
Issuing organization
广东省宝通质量检测有限公司

Recorded Results

Tested specimen 600 x 2400 mm; one window set
Appearance, assembly and construction Pass
Fragmentation 46 and 48 fragments in the indicated 50 x 50 mm assessment area
Watertightness 400 Pa for 15 min; no leakage
Overall conclusion Tested items met the stated requirements; pass

Sample and Test Conditions

  • Client-submitted specimen received 7 October 2025. Testing took place 10-22 October 2025.
  • The inspected report does not state glass thickness. The complete Chinese source includes the original criteria and result table.

The listed tests do not establish an acoustic, thermal, fire-resistance or glazing-seal-life rating.

Related: Cleanroom Doors & Windows

AILV-watermarked cover of document CBT10502182076

Fire integrity

Uninsulated Steel Fire Door

Reported fire-integrity result: E60 (i), 60 min.

CBT10502182076

Read Results & Test Conditions

A fire-integrity test report for a steel fire door with no insulation classification. The report states E60 (i) under GB/T 38252-2019.

Document number
CBT10502182076
Standards
GB/T 38252-2019
Issue date
2025-11-18
Applicant / holder
浙江艾绿净化科技有限公司
Issuing organization
广东省宝通质量检测有限公司

Recorded Results

Tested specimen 900 x 2100 mm; one door set
Reported fire-integrity designation E60 (i) under GB/T 38252-2019
Recorded duration 60 min
Observed result No flames on the unexposed side; no cracks; no loss of fire integrity
Report conclusion Meets the E60 (i) criteria stated in the report

Sample and Test Conditions

  • Client-submitted specimen received 10 November 2025. Testing took place 13-18 November 2025.
  • The complete source contains the furnace-temperature curve and before/after specimen photographs.

This is an integrity-only result for an uninsulated door. E60 (i) is not presented as EI60, and no insulation performance is added.

Related: Cleanroom Doors & Windows

AILV-watermarked cover of document CBT10602183941105

Fire resistance

50 mm MgO / Rock Wool Sandwich Panel

90 min integrity and insulation; reported 50 mm wall assembly.

CBT10602183941105

Read Results & Test Conditions

A commissioned fire-resistance report for a 50 mm metal-faced glass-magnesium (MgO) and rock wool sandwich wall assembly.

Document number
CBT10602183941105
Thickness
50 mm
Standards
GB/T 9978.1-2008; GB/T 9978.8-2008
Issue date
2026-04-17
Applicant / holder
浙江艾绿净化科技有限公司
Issuing organization
广东省宝通质量检测有限公司

Recorded Results

Fire integrity 90 min
Fire insulation 90 min
Mean unexposed-face temperature rise 55 °C at 90 min
Maximum unexposed-face temperature rise 60 °C at 90 min
Geometric-centre deformation +9 mm at 90 min; positive toward the fire-exposed face

Sample and Test Conditions

  • Four submitted panels, each 3000 x 1000 x 50 mm; exposed vertical test assembly 3000 x 3000 mm, with all four edges fixed.
  • Drawing lists 0.5 mm color-coated steel facings, rock wool at 120 kg/m³ and a 5 mm glass-magnesium board layer. It does not identify the material as magnesium oxysulfate.
  • Installation includes steel angles, screws, welded perimeter restraint, silica-alumina fibre joint filler and high-temperature adhesive as specified in the source drawing.
  • The integrity table records no unexposed-face flame at 90 min. The source states that the gap-gauge test was not conducted; no separate claim is made here about cotton-pad subtesting.

The reported 90-minute result applies to the tested wall assembly and fixing details. The 120 kg/m³ rock wool configuration is kept distinct from the 100 kg/m³ configuration in report 2023200610.

Related: 50 mm Single Magnesium & Rockwool Panel

AILV-watermarked cover of document Company registration document

Business registration

Business License (Duplicate)

Company establishment: 20 September 2019.

Company registration document

Read Results & Test Conditions

The supplied business license identifies the AILV legal company and its registered address. It is presented separately from product test reports.

Document number
Company registration document
Issue date
2021-12-28
Applicant / holder
浙江艾绿净化科技有限公司

Company Information

Company name (website English rendering) Zhejiang Ailv Purification Technology Co., Ltd.
Date of establishment 20 September 2019
Registered address No. 186 Ganghang Avenue, Meixi Industrial Park, Anji County, Huzhou, Zhejiang, China
Printed document issue date 28 December 2021

Company Document

  • The original Chinese license contains the full registration particulars. The English page is a reading summary of the business identity information.

Business registration identifies the company; it is separate from product conformity, test performance and certification scope.

Related: About AILV

About Products Contact